Zs Values & Earth Fault Loop Impedance Explained
What Zs values are, how earth fault loop impedance works, the Zs = Ze + R1+R2 formula, and maximum permitted values from BS 7671.
What Is Earth Fault Loop Impedance?
Earth fault loop impedance is the total impedance of the path that fault current takes when a line conductor comes into contact with earth. This path starts at the supply transformer, travels through the line conductor to the point of the fault, through the fault itself, back through the earth path (the circuit protective conductor and main earthing terminal), and returns to the transformer neutral. The impedance of this complete loop is called Zs — the impedance of the earth fault loop.
Zs determines how much fault current will flow when an earth fault occurs. A lower Zs means higher fault current, which causes the protective device (MCB, fuse, or RCBO) to operate more quickly. A higher Zs means lower fault current, which may result in the protective device taking too long to disconnect — or not disconnecting at all. This is why BS 7671 sets maximum permitted Zs values: to ensure that the protective device disconnects within the required time to prevent electric shock.
For socket outlet circuits and circuits supplying portable equipment, the maximum disconnection time is 0.4 seconds. For distribution circuits (those supplying other distribution boards rather than final circuits), the maximum disconnection time is 5 seconds. These times are specified in BS 7671 Chapter 41.
The Zs Formula
The earth fault loop impedance is calculated using a straightforward formula:
Zs = Ze + (R1 + R2)
Each component of this formula represents a different part of the fault loop path:
Ze — External Earth Fault Loop Impedance
Ze is the impedance of the earth fault loop path from the supply transformer to the origin of the installation (typically the main switch in the consumer unit). This includes the impedance of the supply transformer winding, the line conductor from the transformer to the property, and the earth return path back to the transformer. Ze is determined by the electricity supply and the earthing system — it is outside the control of the electrician.
R1 — Line Conductor Resistance
R1 is the resistance of the line (phase) conductor from the distribution board to the point of the fault. This depends on the conductor material (copper or aluminium), the cross-sectional area of the cable, and the length of the circuit. Larger cross-section cables and shorter circuit lengths give lower R1 values.
R2 — Circuit Protective Conductor (CPC) Resistance
R2 is the resistance of the circuit protective conductor (earth conductor) from the distribution board to the point of the fault. In twin-and-earth cables, the CPC is often a smaller cross-section than the line conductor, meaning R2 may be higher than R1. For example, in a 2.5mm² twin-and-earth cable, the CPC is typically 1.5mm².
Measuring R1 + R2
The combined value of R1 + R2 is measured during initial verification using a low-resistance ohmmeter. The test is carried out by linking the line and CPC conductors together at the distribution board and measuring the resistance at the far end of the circuit. This gives the R1 + R2 value directly, which can then be added to the measured Ze to calculate the expected Zs for the circuit.
Typical Ze Values by Earthing System
The Ze value depends on the earthing system of the supply. There are three main earthing systems used in the UK, each with characteristic Ze values. These typical values are published by the Distribution Network Operators (DNOs) and are used during the design stage of an installation.
TN-S (Separate Earth — Cable Sheath Return)
In a TN-S system, the earth return path uses the metal sheath (or armour) of the supply cable. The earth and neutral are separate conductors throughout. Typical Ze values are 0.35 ohms or less, with a maximum design value of 0.8 ohms. TN-S supplies are common in older properties with lead-sheathed or steel-wire-armoured supply cables.
TN-C-S (PME — Protective Multiple Earthing)
In a TN-C-S system, the supply neutral also serves as the earth conductor (a combined PEN conductor) within the supply network. At the origin of the installation, the neutral and earth are separated. Because the neutral conductor provides a low-impedance return path, TN-C-S supplies typically have the lowest Ze values: 0.2 ohms or less, with a maximum design value of 0.35 ohms. This is the most common earthing system in modern UK installations.
TT (Earth Rod)
In a TT system, the installation has its own earth electrode (usually a driven earth rod) with no direct metallic connection to the supply earth. The earth return path goes through the general mass of earth, which has relatively high impedance. Ze values on TT systems are typically 20 ohms or more and can be much higher depending on soil conditions. Because of this high impedance, fault currents on TT systems are too low to operate MCBs or fuses within the required time — which is why RCD protection is essential on all circuits in TT installations.
Always verify Ze on site
The typical values above are design values published by the DNOs. Always measure Ze on site during initial verification or periodic inspection. The actual Ze can differ from the typical value due to cable condition, distance from the transformer, and other factors. Measure Ze at the origin of the installation with the main earthing conductor disconnected from the MET (on TN systems) or with the main switch open (on TT systems using a two-wire method).
Maximum Permitted Zs Values
BS 7671 specifies maximum earth fault loop impedance values to ensure that protective devices disconnect within the required time. These values are found in Chapter 41:
- ✓Table 41.2 — Maximum Zs for circuits protected by BS 88 fuses (HRC fuses)
- ✓Table 41.3 — Maximum Zs for circuits protected by BS EN 60898 Type B MCBs
- ✓Table 41.4 — Maximum Zs for circuits protected by BS EN 60898 Type C MCBs
- ✓Table 41.6 — Maximum Zs for circuits protected by BS EN 60898 Type D MCBs
The maximum permitted Zs value varies depending on the type of protective device and its current rating. The principle is straightforward: the protective device must receive enough fault current to trip within 0.4 seconds (for final circuits) or 5 seconds (for distribution circuits). Since fault current equals voltage divided by impedance (I = V / Zs), a lower Zs produces a higher fault current, ensuring faster disconnection.
For example, a Type B MCB requires a fault current of 5 times its rated current to trip instantaneously. A Type C MCB requires 10 times its rated current. This means that for the same rated current, a Type C MCB has a lower maximum permitted Zs than a Type B MCB — it needs more fault current, so the loop impedance must be lower.
When designing circuits, electricians must ensure that the calculated Zs (Ze + R1 + R2) does not exceed the maximum value for the protective device selected. If it does, either the cable size must be increased (reducing R1 + R2), the circuit length must be shortened, or a different type of protective device must be used.
Related Course
18th Edition (2382)
Understanding maximum Zs values and disconnection times is fundamental knowledge covered in the 18th Edition course.
How Zs Is Measured
Earth fault loop impedance is measured as part of standard electrical testing procedures using a dedicated loop impedance tester. The instrument is connected at the point of use — typically at a socket outlet or at the terminals of a fixed appliance. It passes a brief test current through the earth fault loop and measures the impedance.
Where to Test
Zs readings should be taken at the furthest point from the distribution board on each circuit. This is where the R1 + R2 component is at its highest, and therefore where Zs will be at its maximum. If the reading passes at the furthest point, it will pass at every other point on the circuit.
Comparing the Reading
The measured Zs value must be compared against the maximum permitted value from the appropriate BS 7671 table for the protective device on that circuit. However, the measured value must first be adjusted using the temperature correction factor (Cr).
Testing is carried out at ambient temperature, but under fault conditions the conductor temperature will be much higher, increasing resistance. The correction factor accounts for this difference. The rule of thumb is that the measured Zs value should not exceed 80% of the maximum tabulated value — this provides a safety margin equivalent to the Cr factor for most common cable types and ambient temperatures.
Live testing hazard
Loop impedance testing is a live test — the circuit must be energised for the instrument to measure the fault loop. This means working on or near live conductors. Always follow safe working practices: use properly rated instruments, ensure the test leads and probes are in good condition, wear appropriate PPE, and never carry out live testing unless it is unreasonable to carry out the work dead. A risk assessment should be completed before live testing, as required by the Electricity at Work Regulations 1989.
Alternative Verification Method
Where live loop impedance testing is not practical or not safe, Zs can be determined by calculation: measure Ze at the origin of the installation, measure R1 + R2 for each circuit using a dead test (low-resistance ohmmeter), and add the two values together. This calculated Zs value should then be compared against the corrected maximum tabulated value. This method avoids the need for live testing at every point.
Related Course
Inspection & Testing (2391)
Loop impedance testing and verification methods are core practical skills assessed in the 2391 qualification.
When Zs Is Too High
If the measured or calculated Zs exceeds the maximum value for the protective device, the circuit does not comply with BS 7671. The protective device may not disconnect quickly enough to prevent electric shock. Several remedial options are available:
Increase the CPC Size
Using a larger cross-section CPC reduces R2, which lowers the overall Zs. For example, upgrading from a 1.5mm² CPC to a 2.5mm² CPC will reduce R2 significantly. In some cases, running a separate CPC alongside the existing cable is practical.
Run a Parallel CPC
Installing a supplementary bonding conductor or parallel CPC between the distribution board and the circuit provides an additional earth path, reducing the effective R2. This is sometimes used where re-cabling the entire circuit is not practical.
Reduce Circuit Length
Both R1 and R2 are proportional to circuit length. If the circuit route can be shortened (for example, by relocating the distribution board or re-routing the cable), the overall Zs will decrease. This is primarily a consideration at the design stage rather than a remedial measure.
Use a Larger Cable
Increasing the cross-sectional area of both the line conductor and CPC reduces R1 + R2. For example, upgrading from 2.5mm² to 4mm² twin-and-earth cable will reduce the combined resistance significantly, especially on longer circuits.
Add RCD Protection
Where reducing Zs is not practical, adding an RCD provides supplementary fault protection. When the Zs values are too high, this may be recorded on an EICR as a deficiency requiring remedial action. An RCD will detect earth fault current as low as 30mA and disconnect within 40ms — far faster than any overcurrent protective device. However, an RCD does not reduce Zs; it provides an additional layer of protection. BS 7671 requires RCD protection in many situations regardless of Zs values.
Design stage is key
The most effective way to manage Zs is at the design stage. By selecting appropriate cable sizes and keeping circuit lengths within reasonable limits, you can ensure that Zs will be within the maximum values before installation begins. Use the R1 + R2 values from the IET On-Site Guide tables to calculate the expected Zs for each circuit during design.
Frequently Asked Questions
What is the difference between Ze and Zs?
How do I measure Zs?
Why does the temperature correction factor matter?
What happens if my Zs reading is too high?
Do I need to test Zs on every circuit?
Ready to Start Training?
Browse our City & Guilds accredited courses and take the next step in your electrical career.
Related Guides
How to Calculate Maximum Demand for Electrical Installations
A practical guide to calculating maximum demand — formulae, diversity factors, worked examples, and BS 7671 requirements.
Read guideDiversity Factors Explained: A Practical Guide for Electricians
How to apply diversity factors to electrical circuit loads — tables, worked examples, and when diversity can and cannot be applied.
Read guideVolt Drop Calculations: BS 7671 Limits & Worked Examples
How to calculate voltage drop in electrical circuits — formulae, BS 7671 limits, cable selection tables, and worked examples.
Read guideThree-Phase Power for Electricians: Fundamentals & Applications
Three-phase power explained — how it works, calculations, star and delta configurations, and when electricians encounter it.
Read guide